80IL7800121

FL100

Linear beam smoke detectors

FL100

Linear beam smoke detector Tx + Rx, max range. 150 m. The FL100 linear beam smoke detector is particularly suitable for tertiary sector applications. Its operating principle is based on the interaction between smoke present in an environment generated by a fire and an infrared beam emitted by a transmitting unit (Tx) and received and processed appropriately by a receiving unit (Rx). More specifically, the Rx receiver processes an electrical signal proportional to the intensity of the light received, notifying an alarm or fault condition if the signal falls below an alarm or fault threshold continuously for a predetermined period of time. The detector is equipped with three LED indicators and two 7-segment displays.

  • notification of various types of information to the installer

Technical specifications

Technical specifications

Supply voltage
10,8 ÷ 26,8Vdc
Quiescent current @ 24Vdc
55mA
Quiescent current @ 12Vdc
45mA
Alarm current @ 24Vdc
60mA
Alarm current @ 12Vdc
50mA
Fault current @ 24Vdc
45mA
Fault current @12Vdc
40mA
Pre-alarm obscuration thresholds
20%, 25%, 30%, 35%
Alarm obscuration threshold
35%
Minimum operating distance
5 metri
Maximum operating distance
150 metri
Transmitter beam wavelength
890nm
Beam misalignment tolerance
±1°
Pre-alarm relay
1A, 30Vdc resistive load - selectable NO/NC contact via jumper
Alarm relay
1A, 30Vdc resistive load - selectable NO/NC contact via jumper
Fault relay
1A, 30Vdc resistive load - selectable NO/NC contact via jumper
Conventional line – input voltage range
10 ÷ 20Vdc
Conventional line – pre-alarm absorption
20mA @20Vdc
Conventional line – alarm absorption
40mA @20Vdc
Conventional line – reset pulse duration
200mS
Operating temperature
(-10 ± 3) °C ÷ (55 ± 2) °C
Relative humidity
(93 ± 3)%
Protection degree
IP55
Weight
900 g
Dimensions (L x H x D)
248 x 122 x 120 mm
EN54 part 12 certificate
N. 1293-CPR-0406