80IL7800121
FL100
Linear beam smoke detectors

Linear beam smoke detector Tx + Rx, max range. 150 m. The FL100 linear beam smoke detector is particularly suitable for tertiary sector applications. Its operating principle is based on the interaction between smoke present in an environment generated by a fire and an infrared beam emitted by a transmitting unit (Tx) and received and processed appropriately by a receiving unit (Rx). More specifically, the Rx receiver processes an electrical signal proportional to the intensity of the light received, notifying an alarm or fault condition if the signal falls below an alarm or fault threshold continuously for a predetermined period of time. The detector is equipped with three LED indicators and two 7-segment displays.
- notification of various types of information to the installer
Technical specifications
Technical specifications
- Supply voltage
- 10,8 ÷ 26,8Vdc
- Quiescent current @ 24Vdc
- 55mA
- Quiescent current @ 12Vdc
- 45mA
- Alarm current @ 24Vdc
- 60mA
- Alarm current @ 12Vdc
- 50mA
- Fault current @ 24Vdc
- 45mA
- Fault current @12Vdc
- 40mA
- Pre-alarm obscuration thresholds
- 20%, 25%, 30%, 35%
- Alarm obscuration threshold
- 35%
- Minimum operating distance
- 5 metri
- Maximum operating distance
- 150 metri
- Transmitter beam wavelength
- 890nm
- Beam misalignment tolerance
- ±1°
- Pre-alarm relay
- 1A, 30Vdc resistive load - selectable NO/NC contact via jumper
- Alarm relay
- 1A, 30Vdc resistive load - selectable NO/NC contact via jumper
- Fault relay
- 1A, 30Vdc resistive load - selectable NO/NC contact via jumper
- Conventional line – input voltage range
- 10 ÷ 20Vdc
- Conventional line – pre-alarm absorption
- 20mA @20Vdc
- Conventional line – alarm absorption
- 40mA @20Vdc
- Conventional line – reset pulse duration
- 200mS
- Operating temperature
- (-10 ± 3) °C ÷ (55 ± 2) °C
- Relative humidity
- (93 ± 3)%
- Protection degree
- IP55
- Weight
- 900 g
- Dimensions (L x H x D)
- 248 x 122 x 120 mm
- EN54 part 12 certificate
- N. 1293-CPR-0406