80SD7U00121

FDO400

Optical Smoke Detector

FDO400

Low profile optical smoke detector. Smoke detectors operate on the principle of light scattering caused by smoke particles in the air (TYNDALL effect). The detector has an automatic gain control function; a microcontroller calculates reading compensation to maintain constant sensitivity over time, correcting any increase in level caused by dust deposition inside the analysis cell. Smoke detectors must be installed where there are no drafts that could deflect the flow of particles produced by combustion and in places where normal activities do not produce fires involving gaseous materials.

  • maintenance - green flashing with sequence of yellow flashes indicates fault condition.

Certifications

Certificato EN54 parte 7, N.1293-CPD-0189

Technical specifications

Technical specifications

Supply voltage
20 Vdc (modulated voltage from -15% to + 10%)
Average quiescent current
65 µA @ 20 Vdc
Alarm current
23 mA @ 20 Vdc
3-color LED
red alarm - green normal operation – yellow fault
Minimum reset time
300 mS
Max relative humidity
93%
Operating temperature
-10 °C ÷ +55 °C
Material
ABS V0
Weight
70 g
Dimensions (ø x H)
90 x 31 mm